Characterization of clamp-on current transformers under nonsinusoidal conditions

2009

This paper reports the performance of clamp-on current transformers under nonsinusoidal conditions. A set of experimental measurements helped to determine the ratio and the phase errors under two conditions: 1) sinusoidal excitation with frequencies from 45 to 1000 Hz and 2) nonsinusoidal excitation using the fundamental frequency and one harmonic, with adjusted phase shift. It was found that ratio and phase errors are affected by the phase angle between the harmonic and the fundamental and the harmonic amplitude. The effects of conductor location in the current transformer's window and of the air-gap width were also investigated. It was concluded that harmonic phase and ratio errors measur…

Frequency responseMaterials scienceElectric current measurementTransductorAcousticsErrorsTransducersPhase (waves)Energy Engineering and Power TechnologyClamp-on current transformers current transformers (CTs) frequency response power system harmonics transducers.Power transformersDistributed power generationElectric power systemsHarmonic analysisElectric power transmission networksClamp-on current transformersCurrent transformersFrequency responsePower electronicsFrequency measurementElectronic engineeringElectrical and Electronic EngineeringElectrical conductorTomographyComputed tomographyElectric power distributionElectric transformersCircuit faultsFault currentsFundamental frequencyComputerized tomographyFourier seriesCurrent measurementCurrent transformerDiagnostic radiographyElectric instrument transformersElectric frequency measurementPower system harmonicsMedical imagingCurrent transformers (CTs)Air gap (plumbing)Power transmissionElectric network analysisExcitation
researchProduct